Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 21 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Message  Description 
FCI7100:#28 Err. Invalid Sensor number. 
Expected 1..99 
FCI7100:#29 Err. Invalid Zone number. Expected 
1..255 
FCI7100:#30 Err. Invalid Relay number. Expected 
1..255 
Correct the configuration file.
 4
FCI7100:#31 Err. Point Type Invalid. 
Valid Point Types are listed in Section 
4.4.2
4
FCI7100:#32 Err. No MD Length. Default to 1 
You must specify the 'length' of each Map 
Descriptor. Refer to Section 4.4.2
44
FCI7100:#33 Err. Driver cant poll or write. 
The driver can only listen passively for 
message from the panel. Remove any 
active Map Descriptors from the 
configuration file. 
FCI7100:#36 Err. Too Short. Bytes=%d , conn-
>ux_iptr" 
An event message is less than 80 bytes 
long. If this error is repeated often it is 
possible that a FCI firmware update as 
made the driver unusable. Take a log and 
contact tech support. 
4
 Correct the configuration file, download to the FieldServer and restart the FieldServer for the 
changes to take effect. 