Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 20 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Message  Description 
FCI7100:#12a Err. No MD's to store message 
data. 
FCI7100:#12b Err. No MD's to store message 
data." 
FCI7100:#13 Err. Msg was ignored. MD Required 
for Storage. 
A message arrived and the driver could 
not find a place to store the data. 
Perhaps you were not expecting this type 
of event/this loop/sensor. If you are not 
interested in the data then ignore the 
message. Otherwise update the 
configuration file.
 3
FCI7100:#13a Err. Diagnostic 1); 
FCI7100:#13b Err. Diagnostic 2); 
FCI7100:#13c Err. Diagnostic 3); 
Take a log. Try and repeat the event that 
caused the message to be printed. Then 
contact tech support. 
FCI7100:#14 Err. <%s> file not found., md-
>mapdesc_name ) ; 
FCI7100:#15 Err. Event Type=<%s> Not 
recognized." , drv_bd->event_desc ) 
FCI7100:#16 Err. Point Type='%c'(%#x) Not 
recognized. , drv_bd->point_identifier[0] , drv_bd-
>point_identifier[0] ) ; 
If this error is repeated often it is possible 
that a FCI firmware update as made the 
driver unusable. Take a log and contact 
tech support. 
FCI7100:#17 Err. Loop=%d < 1. Rejected. , 
drv_bd->loop ) 
This message should only be printed if a 
byte in a message has been corrupted. If 
you notice it more than once then take a 
log and contact tech support. 
FCI7100:#18 Err. Loop Type='%c'(%#x) Not 
recognized. , drv_bd->point_identifier[2] , drv_bd-
>point_identifier[2] ) 
If this error is repeated often it is possible 
that a FCI firmware update as made the 
driver unusable. Take a log and contact 
tech support. 
FCI7100:#19 Err. Relay=%d < 1. Rejected. , 
drv_bd->relay 
FCI7100:#20 Err. Zone=%d < 1. Rejected. , 
drv_bd->zone" 
This message should only be printed if a 
byte in a message has been corrupted. If 
you notice it more than once then take a 
log and contact tech support. 
FCI7100:#21 Err. Point Type not recognized 
FCI7100:#22 Err. Undefined Point Type" 
Valid Point Types are listed in section 
4.4.2
3
FCI7100:#23 Err. Event Type not recognized 
FCI7100:#24 Err. Undefined Event Type 
Valid Event Types are listed in section 
4.4.2
3
FCI7100:#25a Err. Address+Length>99. Length 
Truncated 
FCI7100:#25b Err. Address+Length>99. Length 
Truncated 
The maximum value for a sensor/module 
is 99. The combination of address and 
length specified produce a number > 99
3
FCI7100:#26 Err. Invalid Module number. 
Expected 1..99 
FCI7100:#27a Err. Invalid Loop number. Expected 
1..10 
FCI7100:#27b Err. Invalid Loop number. Expected 
1..10 
FCI7100:#27c Err. Invalid Loop number. Expected 
1..10 
Correct the configuration file
3
3
 Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to 
take effect.