Appendix B. Driver Error Messages. 
Message  Description 
FCI7100:#1 FYI. Use a DA called <%s> to expose 
diagnostic info., FCI_7100_STATS_DA ) 
Refer to Appendix B.1 
FCI7100:#2 FYI. Added Event Desc=<%s> 
Index=%d Categ=%d , new_event_desc , 
new_event_desc_index_value , 
new_event_desc_categ ) ; 
Printed for your info only. No action 
required if it confirms your expectations. 
FCI7100:#3 Err. No space. Reject Event 
Desc=<%s> Index=%d , new_event_desc , 
new_event_desc_index_value ) ; 
There is only space for 60 event types.
2
FCI7100:#4 FYI. Duplicate Event Desc=<%s>. , 
new_event_desc ) ; 
You are adding an event type that 
already exists. If you are updating the 
category, ignore the message. Otherwise 
correct the configuration file.
2
FCI7100:#5 FYI. Duplicate Event Desc=<%s>. , 
new_event_desc ) ; 
You are adding an event type that 
already exists. If you are updating the 
index value, ignore the message. 
Otherwise correct the configuration file.
2
FCI7100:#6 Err. Event Index=%d. Too big to set 
bit., drv_bd->event_index ) 
If the event index is greater than 64 then 
the data cannot be stored as bits as only 
64 bits are reserved for events. 
FCI7100:#7a Err. DA=%s too short. Rqd=%d, dt-
>buffer_name , offset ); 
FCI7100:#7b Err. DA=%s too short. Rqd=%d, 
possible_md->data->buffer_name , offset ); 
The MD in question has a length and 
offset which makes it run past the end of 
the Data Array. Message 7b is printed 
when data is being stored as bits.
2
FCI7100:#8 FYI. Reset was rcvd and processed! 
Stamped %s %s , drv_bd->time , drv_bd->date ) 
Printed for your info only. No action 
required. 
FCI7100:#9 Err. Reset was ignored. 
This message is printed when a reset 
was received but for one or more reason 
the driver could not reset any data. Have 
you set 'Clear_on_Reset' to 'no' on all 
MD's ? 
FCI7100:#10 FYI. Reset of DA=%s Off=%d 
Len=%d, possible_md->data->buffer_name , 
possible_md->bxi_data_buffer_offset , 
possible_md->data_length ); 
Printed for your info only. No action 
required.. 
FCI7100:#11 Err. Cant reset DA=%s len=%d 
rqd=%d, possible_md->data->buffer_name ,  
da_get_length_in_items ( (DAH_TYP) 
possible_md->data ) , possible_md-
>data_length+possible_md-
>bxi_data_buffer_offset ); 
The MD in question has a length and 
offset which makes it run past the end of 
the Data Array.
2
2
 Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to 
take effect.