Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 12 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.5.  Map Descriptor Example 1 – Sensor / Module Events 
If messages from Loop 1, Module 1 to 99 are received then the MD in this example will be used for storage. If you have modules on 
more than one loop then you will need one MD for each loop. In this example the event type was set to ‘Alarm’. This means that 
only ‘Alarm’ events will be stored using this MD. This could be useful if you are only interested I one category of events. If you want 
all events stored then change the ‘Event Type’ to ‘Any’. 
Example:
 F.S.E.C. :[CR][LF] 
 FIRST ALARM: UP STAIRS N. ENT Manual Station L1M21 00:37:28 01/01/99[CR][LF] 
// Client Side Map Descriptors 
Map_Descriptors                     
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name, 
Event 
Type, 
Point 
Type, 
Relay/Loop/Zone 
Number, 
Address,  Length,  Clear_on_reset 
ModuleData1,  DA_MODULE,  0,  Passive_Client,  Panel-01,  Alarm,  Module  1,  1,  99,  Yes, 
It is 
recommended 
that you 
allocate unique 
MD names. 
The address 
specifies the 
starting Module 
number and the 
Length tells the 
driver the range 
of Modules. 
In this example: 
Module 1 to 99
Change this to 
‘Sensor’ for 
sensors. 
In this example, 
only Alarm 
events will be 
stored. 
Messages 
reporting other 
events will be 
ignored unless 
other MD’s are 
defined. 
Tell the driver 
the Data Array 
name and 
starting location 
that data should 
be stored. 
The driver 
listens 
passively for 
messages from 
the Panel. It 
cannot poll for 
data. 
The name of 
the Node 
defined in the 
Node 
Descri
p
tor 