User Guide
FS-8700-104_ControlNet_X30 Manual        Page 6 of 13 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.  Configuring the FieldServer as a ControlNet Server 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer 
Configuration Manual. The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” files on the 
driver CD). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a ControlNet Client/Scanner.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In order to enable the FieldServer for ControlNet communications, the driver independent 
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual 
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to 
the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to 
do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the 
default. 
4.1. ControlNet Settings 
Section Title 
FieldServer 
Column Title  Function  Legal Values 
System_Station_Address*  ControlNet MAC ID of the FieldServer  1-99 
Note
: 
The ControlNet MAC ID can also be set via the two rotary switches on the side of the 
FieldServer. These switches should be set to zero or to the same value as 
System_Station_Address in the configuration file. Alternatively the 
System_Station_Address parameter should be eliminated from the configuration file.  
Failing to do so, will cause a warning LED to flash although the MAC ID from the 
configuration file will still be used. 
Example
// FieldServer   
FieldServer   
Title,  System_Station_Address 
CN_Test,  5 