2.  FieldServer as a Modbus Plus Client 
2.1 Hardware Connections  
It is possible to connect a Modbus RTU device to any of the eight RS232 ports or two RS485 
ports. These ports just need to be configured for Modbus RTU in the configuration file. 
Configure the PLC according to manufacturer’s instructions. 
2.2 Configuration File Structure  
Refer to section 4.1 of the Instruction Manual for a description of the operation principle 
of the FieldServer. The following tables describe parameters that need to be filled out in 
the configuration file. For convenience, a few example parameters already exist in the 
supplied PRIMSERV.CSV and SECDSERV.CSV files. 
Note that * indicates an optional parameter, with the bold legal value being the default. 
2.2.1  Data Arrays 
Section Title  
Data_Arrays 
Column Title   Function  Legal Values 
Data_Array_Name  Provide name for Data Array  Up to 15 
alphanumeric 
characters 
Data_Format  Provides data format  INT16, INT32, BIT, 
FLOAT 
Data_Array_Length  Number of Data Objects  1-10,000 
2.2.2  Client Side Connections  
Section Title  
Connections 
Column Title   Function  Legal Values 
Adapter  Adapter name  MBP 
2.2.3  Client Side Nodes 
Section Title  
Nodes 
Column Title   Function  Legal Values 
Node_Name  Provide name for node  Up to 32 
alphanumeric 
characters 
Route  Modbus Plus Path  Note 1* 
Protocol  Specify protocol used  Modbus Plus 
Note 1: Refer to the Modicon user guide 890 USE 102 00 for details on path 
establishment. In general, the first number is the Destination BM85 MAC address, 
the second number represents the internal path, and the third number is the 
destination node. This varies if the BM85 is not connected to the FieldServer. 