37
Specifications
Display: LCD (5 inches diagonal)
Backlight: Blue (adjustable duration)
Low Battery Indication: is displayed when the battery voltage
drops below the operating level.
Over Range Display: OL for pressure, - - - - for temperature
Auto Power Off: 30 minutes of inactivity (adjustable)
Maximum Manifold Pressure: 800 Psig (5500 kPa)
Battery Type: 6 x AA alkaline
Battery Life: 350 hours typical
(without vacuum, backlight, and wireless)
Radio Frequency: 2.4 GHz
Wireless Range: 350 feet (106 meters) line of sight.
Distance decreases through obstructions.
Data Port: Micro USB (for extracting data logs or updating firmware)
Operating Environment: 32°F to 122°F (0°C to 50°C) at <75% RH
Storage Environment: -4°F to 140°F (-20°C to 60°C) at <80% RH
(with battery removed)
Temperature Coefficient: 0.1 x (specified accuracy) per °C (0°C to
18°C, 28°C to 50°C), per 1.8°F (32°F to 64°F, 82°F to 122°F)
Weight: 4.03 lbs (1.83 kg)
Water Resistant: Designed to IP54
US Patent: www.fieldpiece.com/patents
Refrigerants: New refrigerants are continually being added so be
sure to visit www.fieldpiece.com for the latest firmware.
R11
R12
R13
R22
R23
R32
R113
R114
R115
R116
R123
R124
R125
R134A
R236FA
R245FA
R290
R401A
R401B
R402A
R402B
R403B
R404A
R406A
R407A
R407C
R407F
R408A
R409A
R410A
R413A
R414A
R414B
R416A
R417A
R417C
R420A
R421A
R421B
R422A
R422B
R422C
R422D
R424A
R427A
R428A
R434A
R438A
R448A
R449A
R450A
R452A
R452B
R453A
R454B
R458A
R500
R501
R502
R503
R507A
R508B
R513A
R600
R600A
R601
R601A
R744*
R1233ZD
R1234YF
R1234ZE
*Maximum pressure: 580 Psig (4000 kPa)
Temperature
Sensor Type: Type K thermocouple
(nickel chromium/nickel aluminum)
Jack Type: (3) Type K thermocouple
Range: -50°F to 257°F (-46°C to 125°C), limited by the thermocouple
specification. Display range is -95°F to 999.9°F (-70°C to 537.0°C).
Resolution: 0.1°F (0.1°C)
Accuracy: Shown accuracies are after field calibration.
±(1.0°F) -95°F to 200°F, ±(2.0°F) 200°F to 999.9°F;
±(0.5°C) -70°C to 93°C, ±(1.0°C) 93°C to 537.0°C
Pressure
Sensor Type: Absolute pressure sensors
Port Type: (3) 1/4” standard NPT male flare fittings
Pressure Range and Units: 580 Psig (English), 40.00 Bar (Metric),
4.000 MPa (Metric), and 4000 kPa (Metric)
Negative Pressure Range and Units:
29 inHg (English), 74 cmHg (Metric)
Resolution: 0.1 Psig; 0.01 Bar; 0.001 MPa; 1 kPa; 0.1 inHg; 1 cmHg
Negative Pressure Accuracy:
29 inHg to 0 inHg: ±0.2 inHg;
74 cmHg to 0 cmHg: ±1 cmHg
Pressure Accuracy:
0 Psig to 200 Psig: ±1 Psig;
200 Psig to 580 Psig: ±(0.3% of reading + 1 Psig);
0 Bar to 13.78 Bar ±0.07 Bar;
13.78 Bar to 40.00 Bar: ±(0.3% of reading + 0.07 Bar);
0 MPa to 1.378 MPa: ±0.007 MPa;
1.378 MPa to 4.000 MPa: ±(0.3% of reading + 0.007 MPa);
0 kPa to 1378 kPa: ±7 kPa;
1378 kPa to 4000 kPa: ±(0.3% of reading + 7 kPa)