Replacement Parts List

page 6
AIR ADJUSTMENT
Adjust the air adjustment knob on the side of the Air Boot to rough air setting (See Table 2). 1.
NOTE: For proper burner operation, burner should be set up by using a combustion analysis test set.
Start the burner and adjust the air control as needed to achieve the required CO2.
2
and smoke levels. Set
over fire draft to appliance manufacturers' specifications (typically -.02" of water). Secure air control knob
with indicator bracket. If draft levels are not obtainable or controllable, use standard industry methods to
control the draft or call the Field Controls Tech Line at 1-800-742-8368 for more information, or check the
website at www.fieldcontrols.com.
Next, adjust the VRV gate by screwing the adjustment weight in until the VRV gate is just closed.3.
Re-check the burner’s operation and adjust accordingly.4.
Lock the adjustment weight in position by tightening the hex nut on the VRV gate.5.
ROUGH AIR SETTING
GPH
Knob Setting
CAS-2B CAS-2C CAS-2W
.75 25º 15º 70º
1.00 60º 25º 90º
1.50 160 º 105º 135º
Table 2