Specification

11
PV
(Indoor Mounted Power
Venters for Oil & Gas)
PVG - Gas and PVG PAK
Maximum Equivalent Horizontal Pipe Length (Feet)†
Model
(BTU/hr Input)
DIA.
25,000 55,000 70,000 100,000 145,000 220,000 310,000 400,000 520,000 610,000 900,000 1,250,000
PVG-100
PVGPAK-100*
3"
270 100
4"
455 169 144 100
PVG-300
PVGPAK-300*
PVU-300
4"
305 145 64
5"
247 100 54
6"
334 147 74
PVG-600
5"
413 181 91 54
6"
146 87 52
8"
216 134 86 66
PVE-1200**
8"
313 180
10"
390 290 80
PVO - Oil
Maximum Equivalent Horizontal Pipe Length (Feet)†
Model DIA.
GPH Input
0.40 0.50 0.75 1.00 1.50 2.25 3.00 3.75 4.00 6.00 9.00
PVO-300
PVU-300
4"
287 150 75
5"
257 120 51
6"
346 172 70
PVO-600
5"
428 212 86 46
6"
143 74 51
8"
211 116 84 77
PVE-1200*
8"
436 385 208
10"
407 311 74
Power Venters
† See calculating equivalent feet of a vent system
* PVG PAKs include a Power Venter, a 4" MG-1 Draft Control, and a 4" Vent Hood.
** PVE-1200 requires a CK-Kit.
D
H
Specifications
See calculating equivalent feet of a vent system
* PVE-1200 requires a CK-Kit.
Select venter according to the actual rated maximum GPH Input. GPH ratings at 100 PSI.
Do not exceed maximum oil GPH Input.
UNIT DIMENSIONS (INCHES) ELECTRICAL DATA
Model
Height Width Depth Inlet/Outlet Volts Hz RPM Watts Amps Therm. Prot.
PVG/PVO-100
7.50 7.75 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO/PVU-300
7.50 9.25 7.00 4.00 115 60 3000 145 2.1 YES
PVG/PVO-600
8.75 9.75 8.50 5.00 115 60 3000 167 1.5 YES
PVE-1200
13.75 11.50 13.50 8.00 115 60 1750 186 3.9 YES
Note: New universal Power Venter (model PVU-300) now available.