CONNECTING POWER VENTER TO APPLIANCE
Venting system should be installed and supported in accordance with the National Fuel Gas Code ANSI
Z223.1, or in accordance with any local codes. A vent pipe connector shall be supported for the design and
weight of the material employed, to maintain clearances, prevent physical damage and separation of joints. A
vent pipe increaser or reducer may be required for connecting the power venter to the vent system. If needed,
place the reducer close to the power venter. Smaller vent pipe sizes than a chimney-vented system may be
used for the vent system.
If mounting venting system near combustible materials, refer to Diagram B for allowable installation
clearances. Clearances are based on an installation using single wall galvanized steel vent pipe. For metal
thickness of galvanized steel pipe connectors, refer to NFPA 211 or NFPA 54 Standards for guidelines. If
manufactured double wall vent pipe is required or used for the installation, clearance should be based on the
vent pipe’s rated clearance. Always check local code requirements for code restrictions.
Route the vent pipe from the appliance to the power venter using as few elbows as possible. The horizontal
section of the vent pipe should have a slight upward slope from the appliance to the power venter. For
clearances to combustible materials, multiple appliance venting and other installation requirements, refer to
the National Fuel Gas Code ANSI Z223.1, and/or any applicable local codes or appliance manufacturer’s
installation instructions.