CK-20F/HWK:
For operation with 30 or 750 millivolt gas- red water heaters, gas- red space heaters, and gas-
red pool or spa heaters with an internally mounted thermostat. Includes a  xed post purge.
CK-21:
For operation with gas- red instantaneous water heaters with a pressure tap port in the
burner manifold.
CK-40F/41F:
For operation with gas- red furnaces, boilers, unit heaters and water heaters operating with a
24 VAC gas valve. For systems not equipped with factory mounted spillage switches, use the
CK-41F which includes two GSK-3 spill switches. Includes a  xed post purge.
CK-43/43F:
For draft induced 24 VAC gas valve systems. Includes a 4” MG-1 draft control and electronic
post purge. The CK-43F includes a  xed post purge.
CK-61:
For operation with oil- red systems. Has electronic post purge.
CK-62:
For operation with oil- red systems. Has thermally activated post purge.
CK-63:
For operation with oil- red systems. Has electronic post purge. For operating venter with or
without burner motor.
CK-81:
For operation with 750 millivolt operated boilers, furnaces, water heaters, pool or spa heaters,
and gas- red replaces when operating with remote mounted thermostat. Operated o a 24
VAC thermostat. For operation o of a 120 VAC thermostat or wall switch, use the CK-80.
CK-91/91F:
For gas  red draft induced 24 VAC gas valve systems and a 30 millivolt operated water heater.
Includes a 4” MG-1 draft control and an electronic post purge. The CK-91F includes a  xed post
purge.
CK-92/92F:
For operation with gas- red furnaces, boilers, unit heaters and water heaters operating with a
24 VAC gas valve and a 30 millivolt operated water heater. Includes an electronic post purge.
The CK-92F includes a  xed post purge.
CONTROL KITS
INSTALLATION SAFETY INSTRUCTIONS
CAUTION: This device must be installed by a quali ed installer in accordance with the manufacturer's installation
instructions. Appliances should have a minimum of 75% combustion e ciency or have a maximum measured  ue
gas temperature of 550°F (Stainless steel units maximum temperature rating 650°F US/575°F CA) at the inlet of
the power venter.
1. The power venting system must be installed by a quali ed installer. "Quali ed Installer" shall mean an
individual who has been properly trained or a licensed installer. The installer must write or imprint his name,
phone number and date of installation on the installation tag. The tag should be attached to the power
venting system control kit box or power venter unit. Recording burner and venting system initial operational
information is strongly recommended as a guide for service or burner tune-up. Enter this in the space later in
this manual.
2. Safety inspection of a venting system should be performed before and after installing a power venting system
on an existing or new appliance. Procedures to follow are those recommended by the National Fuel Gas
Code ANSI Z223.1, or refer to the General Installation Inspection section of this manual.
3. Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed
wiring or plumbing inside walls.
4. Single wall vent pipe (refer to Diagram B) may be used to join an appliance to the venting system, but if
proper clearances cannot be maintained from combustible materials, Class B Vent Pipe should be used for
gas appliances and Class L Type Vent Pipe for oil appliances. Refer to national or local codes for guidelines.
5. Disconnect power supply before making wiring connections to prevent electrical shock and
equipment damage.
6. This equipment is designed to overcome minor negative pressure conditions. To ensure extreme negative
pressure does not exist, follow the General Installation Inspection section of this manual.
7. Heating appliances equipped with draft hoods, such as boilers or furnaces, LP gas appliances, and Natural
gas appliances SHOULD have a secondary spillage switch installed. On appliances without draft hoods, it is
recommended that a secondary safety switch such as a WMO-1, GSK, FTS, or TSP-1 be used. Gas- red 30
millivolt power systems MUST be equipped with a spillage switch.