4. System Safety Devices: With the heating system operating disconnect the pressure sensing
tube from the pressure switch on the CK kit. This should stop the burner operation. Re-
connecting the tube will relight the burner. For 30 millivolt operating systems, disconnect
one lead of the spill switch circuit from the thermocouple junction block. This should shut off
the pilot and the burner. Re-connection will allow relighting the pilot.
XI. REPLACEMENT PARTS
The following items are available for replacement, if necessary.
Replacement Parts List
Part Number Description
46032000 PVE-100 Motor
46032000 PVE-300 Motor
46083300 PVE-600 Motor
46226500 PVE-1200 Motor
46080100 PVE-100 Blower Wheel
46033400 PVE-300 Blower Wheel
46089400 PVE-600 Blower Wheel
46124000 PVE-1200 Blower Wheel