WIRING 
All electrical work and materials used in the vent damper installation shall 
be in accordance with local electrical codes. In the absence of codes, 
consult the National Electrical Code. 
To avoid damage to the room thermostat heat anticipator turn off the 
electrical power supply to the appliance before proceeding with the wiring. 
CAUTION: Electronic Thermostats 
Problems can occur with the use of some electronic thermostats. Some 
electronic thermostats rob power through the thermostat circuit to maintain 
the thermostat programming. For these types of installations an isolation 
relay is recommended. This will eliminate possible erratic cycling of the 
damper, the thermostat or the appliance controls. Another option is to 
install a non-power stealing type of thermostat. (See Figure 8) 
PROBLEM/SOLUTION GUIDE
CAUTION: When servicing controls, all wires must be labeled prior to 
disconnection. Wiring errors can cause improper and dangerous operation. Do 
not turn damper open manually or motor damage will result and Void the 
Warranty, use the service switch. 
DO NOT CUT PLUG OFF OF DAMPER MOTOR ASSEMBLY OR WARRANTY WILL BE VOID. 
WARNING: Do not negate the action of any existing safety or operational controls 
N
ORMAL SEQUENCE OF OPERATION 
24VAC 
POWER 
Power On  Damper Position 
4&1  All Times  Open or Closed 
4&2  Calling for Heat  Open or Opening 
4&3  During Combustion  Damper Open 
Figure 8