UNPACKING INSTRUCTIONS 
1.  The Field Controls GVD Series Gas Vent Damper is packaged in a single carton containing an assembled GVD, instruction 
manual and a plug. NOTE: Some OEM supplied units have the wiring harness attached. 
2.  Inspect for damage prior to the installation. 
3.  Retrofit installations require a wire harness. Order the universal wire harness #46390008. 
PRE-INSTALLATION WARNINGS
1.  The Field Controls Automatic Vent Damper must be installed by a qualified installing agency in accordance with the 
manufacturer’s installation instructions. The definition of a qualified installation agency is:  any individual, firm, corporation or 
company which either in person or through a representative is engaged in, and is responsible for, the installation and operation 
of gas appliances and automatic vent damper devices, who is experienced in such work, familiar with all the precautions 
required, and has complied with all the requirements of the authority having jurisdiction. The qualified installer shall fill in the 
installer’s name, address and installation date on the label attached to the vent damper device. 
2.  Do not negate the action of any existing safety or operational controls. 
3.  When servicing controls, all wires must be LABELED prior to disconnection. Wiring errors can cause improper and dangerous 
operation. 
4.  Device must be installed by a qualified installer, in compliance with local codes or the National Fuel Gas Code (ANSI Z223.1 
NFPA 54 or CAN/CGA-B149) and the National Electric Code (ANSI C1-NFPA 70). 
5.  Device conforms to ANSI Z21.66. CSA design certified. 
6.  Use only with a listed gas fired appliance equipped with a draft hood, the outlet area of which is not greater than the inlet area 
of the device. 
7.  Install after the appliance draft hood, as close to the draft hood as practicable, and without modification to the draft hood or the 
vent damper. 
8.  Locate in a venting system or section of a venting system so that it services only the single appliance for which it is intended. 
9.  A minimum clearance of 6 inches (153mm) between the damper device and combustible construction must be maintained 
and that there be provisions for access and service of the damper device. 
10.  Position indicator and service switch must be accessible to the user. 
11.  The installer must fill in the label on the side of the motor assembly cover. 
12. This device must be installed only on a listed gas appliance connected to a factory built chimney or vent complying with a 
recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having 
jurisdiction. 
13.  This vent damper device shall not be installed on an appliance with an automatic valve having a manual valve control unless 
the manual valve control has been rendered in-operative or the automatic valve has been replaced with a redundant automatic 
valve not equipped with a manual valve control. 
PRE-INSTALLATION INSPECTIONS
P
ROCEDURE FOR SAFETY INSPECTION OF AN EXISTING APPLIANCE INSTALLATION 
The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in a safe condition 
for continuing use. 
This procedure is predicated on central furnace, boiler and water heater installations, and it should be recognized that generalized 
procedures cannot anticipate all situations. Accordingly, in some cases deviation from this procedure may be necessary to 
determine safe operation of the equipment. 
1.  This procedure shall be performed prior to installation of the automatic vent damper device. 
2.  If it is determined there is a condition which could result in unsafe operation, the appliance should be shut off and the owner 
advised of the unsafe condition. Do not install the automatic vent damper device until the unsafe condition has been corrected. 