Brochure
Page 10
WARNING: For trouble shooting only. Make sure damper is in the open position. Use the service switch to keep the 
damper in the open position. Place a jumper between 2 & 3. If the appliance fires, remove jumper & plug receptacle back 
into damper controller plug. If appliance does not fire, replace damper motor assembly. Do not replace the pipe assembly. 
If a damper motor assembly is not available, place the service switch in the hold open position. This should keep the 
damper in the open position and allow the customer to have automatic heat. Return or replace the motor assembly at 
your convenience. The motor assembly carries an 18 month limited commercial warranty from the original date of 
manufacturing (Refer to form #4294 on website). Pipe assembly will not be warranted. 
PROBLEM  POSSIBLE CAUSE  RECOMMENDED SOLUTION 
NO POWER 
Between 4&1 
1.  Off on limit (120VAC) 
2. Bad Transformer. 
3.  Loose or broken connections. 
4.  Blown fuse or circuit breaker. 
5.  Disconnect switch off. 
6.  Harness not plugged into appliance 
receptacle. 
1.  Turn limit on. 
2. Replace transformer. 
3.  Tighten, repair or replace connection. 
4.  Replace fuse or reset circuit breaker. 
5.  Turn Switch on. 
6.  Plug harness in. 
NO POWER 
Between 4&2 
POWER 
Between 4&1 
When Calling For Heat 
1.  Thermostat not calling for heat. 
2.  Burned out heat anticipator. 
3.  Loose or broken connections. 
4.  Off/On operating limit, pressure 
control or low water cut off. 
5.  Off/On blocked vent switch or 
flame roll out 
1.  Turn thermostat up to call for heat. 
2. Replace thermostat 
3.  Tighten, repair or replace 
connection. 
4.  Turn operating limit, pressure 
control or lower water cut off on. 
5.  Reset or replace switch. 
POWER 
Between 4&1 
Between 4&2 
DAMPER OPEN 
1.  Loose or broken connection. 
2.  Defective damper motor. 
1.  Tighten, repair or replace 
connection. 
2.  Replace damper motor assembly. 










