Product Overview
Table Of Contents
FIELD CONTROLS, LLC - CONTRACTOR PRODUCTS SWG and POWER VENTING SYSTEMS
Dimensions (inches)
Model Pipe Size Length Height Clearance Exposed Pipe
A B C D E
GVD-4PL 4 6 1/16 8 7/8 15/16 4 13/16
GVD-5PL 5 6 1/16 9 7/8 15/16 4 13/16
GVD-6PL 6 6 1/2 10 7/8 1 3/16 5 1/4
GVD-7PL 7 7 1/16 11 7/8 1 7/16 5 13/16
GVD-8PL 8 8 1/16 12 7/8 1 15/16 6 13/16
GVD-9PL 9 10 1/8 13 7/8 3 8 7/8
GVD-10PL 10 12 1/8 14 7/8 4 10 7/8
GVD-12PL 12 12 1/8 16 7/8 4 10 7/8
All dimensions are in inches and are approximate. Specifications subject to change. For the most current
specifications, contact Field Controls.
How the GVD Works
The Field Vent Damper is installed in the vent pipe, after the draft hood, or barometric. During off cycles,
it remains closed, or preventing air flow through the vent. When there is a call for heat, the motor is
energized, rotating the damper 90 degrees to an open position. Opening and closing takes approximately
15 seconds. When the damper is fully open, the burner is allowed to fire and flue gases pass freely
through the vent. When the thermostat is satisfied, the burner stops, and the damper automatically closes.
For service and trouble shooting, the damper can be locked in the open position.
Electrical Specifications
• Minimum wiring requirements: 24 VAC • 18 gauge • 105ºC
• Power requirements: 3 watts at 24 VAC, 60 Hz, when opening or closing
http://fieldcontrols.com/gvd.php (2 of 3)5/9/2007 1:50:31 PM