ELECTRICAL DATA
VOLTS AMPS HZ WATTS RPM THERMAL OR IMPEDANCE PROTECTION
120 VAC .60 60 35 3000 YES
A permanent wiring method must be used for power connection. It is recommended that a minimum size of 14 AWG wire
for electrical supply connections and wiring should be suitable for 60°C (180°F) temperature. The ELIMINATOR
TM
should
be wired with an over current protection device (fuse or circuit breaker) rated 15 amperes or less. Wiring method should
be in accordance with the National Electrical Code and any local code requirements.
WIRING (See Figures 5 & 6)
Figure 5
Figure 6
SINGLE UNIT MULTIPLE UNIT