TROUBLE SHOOTING HINTS
1. Venter does not activate when thermostat calls for heat.
a. Check wiring: 115 VAC from L1 to ground; N connected to a neutral.
b. Check for 24V from orange to black wires on base of timer relay. If no other voltage, the appliance is
not calling for heat to the CK-92. If there is 24 volts continuously for at least 45 seconds there should
be 115 volts from N to M. If not, the time relay is defective, or L1 and N are not properly wired.
c. Check gas pressure switch for continuity across terminals when water heater burner is lit.
2. Flue gas odor:
a. Check system draft. Adjust power venter's air ow adjustment damper if necessary.
b. Check for negative pressure in building.
3. Venter activates but burner does not re after a minimum of 45 seconds continuous call for heat:
a. Check wiring.
b. Check pressure switch adjustment.
c. Make sure the vent damper is in open position.
d. Check for 24 volts from both yellow wires on pressure switch to black wire on base of timer relay. If
neither yellow wire has 24 volts, the vent damper is defective, has loose wiring, or is not receiving call
for heat on the orange wire. If one yellow wire has 24 volts but the other does not, the pressure switch
is not closing.
4. Pilot will not stay lit on water heater:
a. Solder all spillage switch wire terminal connections.
b. Check reset buttons on spillage switches.
Model Part Number
Gas Pressure Switch 46284200
GSK-3 Spillage Switch 46086400
Post Purge Timer 46282800
Pressure Switch 46273100
TCA-1 Thermocouple 46082700
Wire Harness 46457200
REPAIR AND REPLACEMENT PARTS LIST
This manual may be downloaded and printed from the Field Controls website (www. eldcontrols.com)
This manual may be downloaded and printed from the Field Controls website (www. eldcontrols.com)
WARRANTY
WARRANTY
For warranty information about this or any Field Controls product, visit:
For warranty information about this or any Field Controls product, visit:
www. eldcontrols.com/ventCool
www. eldcontrols.com/ventCool
Field Controls Technical Support
Field Controls Technical Support
1.800.742.8368
1.800.742.8368
eldtec@ eldcontrols.com
eldtec@ eldcontrols.com