Submittal Sheet

Page 4
TROUBLE SHOOTING HINTS
1. Venter does not activate when thermostat calls for heat.
a. Check wiring.
b. Check gas pressure switch for continuity across terminals when gas valve is pressurized.
c. Check gas pressure.
2. Flue gas odor:
a. Check system draft.
b. Check for negative pressure in building.
3. Pilot will not stay lit on water heater:
a. Solder all spillage switch wire terminal connections.
b. Check reset buttons on spillage switches.
c. Use 12 gage wire for all spillage switch wiring.
d. Check for interruption of supply power.
REPAIR AND REPLACEMENT PARTS LIST
REPAIR AND REPLACEMENT PARTS LIST
DESCRIPTION PART NUMBER
Gas Pressure Switch 46284200
GSK-3 Spillage Switch 46086400
Thermocouple Junction Box 46082700
INSTALLATION INFORMATION
MODEL NO.:____________________________________________________________
INSTALLER'S NAME:_____________________________________________________
INSTALLER'S COMPANY: _________________________________________________
INSTALLER'S PHONE NO.: ________________________________________________
DATE OF INSTALLATION:_________________________________________________
CK-20F
P/N 46285000 Rev G 02/04