SPECIAL VENTING APPLICATION INSTALLATION SHEET 
This sheet covers the requirements for installation of the 
Starkap™ for use with attached buildings designed for the 
purpose of housing heating equipment outside of the living 
space of the structure. These requirements are based on 
A.G.A. test reports C-FT-5-90, C-FT-8-90, FT-C-12-93 AND 
FT-C-13-93. See Figure 4 and 5. 
1.  The maximum gas heating appliance (or multiple 
appliances ) up to 250,000 BTU/HR input. 
2.  Each appliance in the building MUST have its own separate 
vertical vent and Starkap™. 
3.  The connecting wall between the attached building and the 
main structure MUST be sealed to prevent flow into the 
main structure. Example: Attached garages must be 
sealed by lining ceiling and any wall adjacent to the living 
space with 1/2" thick gypsum board or equivalent. 
Openings from an attached garage directly into a room 
used for sleeping purposes shall not be permitted. Other 
openings between the garage and residence shall be 
equipped with either solid wood doors not less than 1-3/8" 
in thickness or 20-minute fire-rated doors, or equivalent. 
4.  Two make up/combustion air openings into the outside 
building shall be installed. Size of the openings shall be 10 
inch by 10 inch or based on 1 sq. inch per 4000 BTU/HR. 
5.  Termination location shall have a 4 ft. 9 in. center line 
distance from any vertical wall up to 250,000 BTU/HR. 
Termination location for up to 40,000 BTU/HR water heaters shall be a minimum 1 ft. 6 in. center 
line distance from any vertical wall. A minimum height of 12 inches shall be maintained above the 
roof. 
6.  The vent termination shall be located at least 4 feet from any window or opening into the main 
building structure. 
Figure 4
Figure 5