Submittal Sheet

FIELD CONTROLS, LLC - CONTRACTOR PRODUCTS DRAFT CONTROLS
Recommended Locations for Field Draft Controls
For gas-fired equipment, the preferred location of the control is on the bull head tee. This location provides maximum relief of
downdrafts with minimum positive pressure. (See Fig. 1, Dia. A-C)
With oil or solid fuels, the bull head tee is not recommended, so instead, locate the control as shown. (See Fig. 1, Dia. D-J)
These locations are acceptable for gas units as well. Except on forced draft systems, locate the control as close as possible to
the furnace or boiler, at least 12" beyond a stack switch on oil-fired units, and at least 18" from a combustible ceiling or wall.
Commercial and industrial furnaces and boilers are frequently installed in multiples.
(See Fig. 2)
Use a draft control for each boiler located on the uptake between the smoke outlet and the breaching (location A). When this
uptake is too short to permit the installation of a control, locate a separate control for each boiler on the main breaching
(location B). If neither of these locations is possible, use a single large control in the breaching between the chimney and the
nearest boiler (location C).
Where several units are vented into a common breaching, the most draft-critical should vent highest in, or be placed closest to
the chimney. Incinerators should generally be placed farthest from, or vented lowest in the chimney.
BACK TO TOP