Install Instructions
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage 
or blindness.Never operate the UV-Aire
™
 Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.
Page 7 of 12
P/N 46648100 09/18 Rev J
REPLACEMENT PROCEDURE (LAMP ONLY)
WARNING:
WARNING:
 Disconnect power to the transfomer 
 Disconnect power to the transfomer 
or unplug the  
or unplug the  
120V power 
120V power 
cord 
cord 
before starting replacement 
before starting replacement 
         procedure
         procedure
.
NOTE: Wear disposable, non-absorbent protective gloves prior to 
       replacement procedure in case of accidental breakage of 
     glass.
1. Rotate the Duo or UV-Aire ballast assembly counter-clockwise 
until it stops. (See Figure 9)
2. Remove the ballast assembly and lamp from the mounting base. 
(See Figure 10)
3. Remove the lamp from the lamp socket.
4. Install the replacement lamp into lamp socket. Do not handle the 
lamp with bare hands. Oils on the hands tend to reduce lamp 
intensity.
5. Wipe off the glass with the supplied alcohol wipe.
6. Position the ballast assembly power cord 90° to the viewport 
hole on the mounting base. (See Figure 10)
7. Slide the lamp through the hole in the mounting base.
8. Press the ballast against the mounting base. Rotate the ballast 
assembly clockwise until it stops and is locked in place. (See 
Figure 11)
9. After assembly is fi rmly in place, reconnect power to transformer 
or ballast. Check lamp operation by looking through the viewport 
hole. A blue glow should be seen in the duct.
10. After replacing the lamp, make sure to install the Lamp 
Replacement Label. Print the date on the label and apply to the 
side of ballast assembly.
Figure 9 (Removal)
Figure 10
MAINTENANCE
WARNING: Disconnect power to the transformer before commencing 
WARNING: Disconnect power to the transformer before commencing 
inspection and cleaning.
inspection and cleaning.
NOTE: Wear disposable, non-absorbent protective gloves prior to inspection procedure in case of accidental 
      breakage of glass.
1. We recommend inspecting and cleaning the lamp at least every 6 months. Frequency depends upon the 
environment. Such as: the type of air fi lter, duration of use and replacement cycle.
2. To maintain maximum output intensity, replace the UV-Aire lamp annually. The lamp should operate 
continuously for maximum lamp life and light effectiveness.
3. Do not attempt to clean the catalytic honeycomb core with cleaning solutions. The catalyst is radiated with 
short wave ultraviolet light during period of non-air fl ow and is self-cleaning. If there is build up blocking 
the catalytic cells, sit the unit on end, on a fl at surface, with electrical enclosure facing up. Use low-pressure, 
compressed air to blow the surface of the catalytic cells free of blockage.