User's Manual
22
ADVANCED PARAMETERS
51. First channel - minimal time between power reports
This parameter determines minimum time that has to elapse before
sending new power report to the main controller
.
Available settings: 0 - reports are disabled
1-120 (1-120s) - report interval
Default setting: 10 (10s) Parameter size: 1 [byte]
53. First channel - energy reports
This parameter determines the minimum change in consumed ener-
gy that will result in sending new energy report to the main controller.
Available settings: 0 - reports are disabled
1-32000 (1-32000Wh) - change in energy
Default setting: 100
(100Wh)
Parameter size: 2 [bytes]
54. Second channel - power reports (FGS-223 only)
This parameter determines the minimum change in consumed power
that will result in sending new power report to the main controller.
Available settings: 0 - reports are disabled
1-100 (1-100%) - change in power
Default setting: 20 (20%) Parameter size: 1 [byte]
55. Second channel - minimal time between power reports
(FGS-223 only)
This parameter determines minimum time that has to elapse before
sending new power report to the main controller
.
Available settings: 0 - periodic reports are disabled
1-120 (1-120s) - report interval
Default setting: 10 (10s) Parameter size: 1 [byte]
57. Second channel - energy reports (FGS-223 only)
This parameter determines the minimum change in consumed ener-
gy that will result in sending new energy report to the main controller.
Available settings: 0 - reports are disabled
1-32000 (1-32000Wh) - change in energy
Default setting: 100
(100Wh)
Parameter size: 2 [bytes]
58. Periodic power reports
This parameter determines in what time interval the periodic power
reports are sent to the main controller
.
Available settings: 0 - periodic reports are disabled
1-32000 (1-32000s) - report interval
Default setting: 3600 (1h) Parameter size: 2 [bytes]