User's Manual
17
ADVANCED PARAMETERS
56. Low temperature alarm threshold
If temperature is lower than the set value, underheat notication will
be sent and low temperature scene will be triggered (if activated).
Available settings: -300-700 (-30-70°C, 0.1°C step)
Default setting: 40 (4°) Parameter size: 2 [bytes]
70. Scene activation functionality
The device can trigger scenes using scene IDs assigned to dierent
events.
To deactivate all scenes set the value to 0. To activate all scenes set
the value to 3903.
Available settings: 1 - [ID 10] opening door/window (single click)
2 - [ID 11] closing door/window (single click)
4 - [ID 12] holding
8 - [ID 13] releasing
16 - [ID 14] double click
32 - [ID 15] triple click
256 - [ID 50] high temperature - door/window
opened
512 - [ID 50] high temperature - door/window
closed
1024 - [ID 51] low temperature - door/window
opened
2048 - [ID 51] low temperature - door/window
closed
Default setting: 0 (none) Parameter size: 2 [bytes]
71. Alarm broadcast
Settings for broadcasting ON/OFF commands, sensor alarm and tam-
per alarm. Value other than 0 means alarms are sent in Broadcast
Mode, to all devices only within the range of the device. They are not
repeated by the mesh network.
Available settings: 0 - broadcasts inactive
1 - ON/OFF commands broadcast active
2 - sensor alarm broadcast active
4 - tamper alarm broadcast active
Default setting: 0 (inactive) Parameter size: 1 [byte]
CAUTION
Every activated scene
may shorten the bat-
tery life.
!
NOTE
Values of parameter
71 may be combined,
e.g. 1+2=3 means
ON/OFF commands
and sensor alarm
are sent in Broadcast
Mode.
i
NOTE
Values of parameter
70 may be combined,
e.g. 1+2=3 means
scenes for opening
and closing are sent.
i
NOTE
Scenes with IDs 12 to
15 are active only if
parameter 1 is set to
1. In this case scenes
with IDs 1 and 2 are
sent after a single click.
i