User's Manual

17
ADVANCED PARAMETERS
56. Low temperature alarm threshold
If temperature is lower than the set value, underheat notication will
be sent and low temperature scene will be triggered (if activated).
Available settings: -300-700 (-30-70°C, 0.1°C step)
Default setting: 40 (4°) Parameter size: 2 [bytes]
70. Scene activation functionality
The device can trigger scenes using scene IDs assigned to dierent
events.
To deactivate all scenes set the value to 0. To activate all scenes set
the value to 3903.
Available settings: 1 - [ID 10] opening door/window (single click)
2 - [ID 11] closing door/window (single click)
4 - [ID 12] holding
8 - [ID 13] releasing
16 - [ID 14] double click
32 - [ID 15] triple click
256 - [ID 50] high temperature - door/window
opened
512 - [ID 50] high temperature - door/window
closed
1024 - [ID 51] low temperature - door/window
opened
2048 - [ID 51] low temperature - door/window
closed
Default setting: 0 (none) Parameter size: 2 [bytes]
71. Alarm broadcast
Settings for broadcasting ON/OFF commands, sensor alarm and tam-
per alarm. Value other than 0 means alarms are sent in Broadcast
Mode, to all devices only within the range of the device. They are not
repeated by the mesh network.
Available settings: 0 - broadcasts inactive
1 - ON/OFF commands broadcast active
2 - sensor alarm broadcast active
4 - tamper alarm broadcast active
Default setting: 0 (inactive) Parameter size: 1 [byte]
CAUTION
Every activated scene
may shorten the bat-
tery life.
!
NOTE
Values of parameter
71 may be combined,
e.g. 1+2=3 means
ON/OFF commands
and sensor alarm
are sent in Broadcast
Mode.
i
NOTE
Values of parameter
70 may be combined,
e.g. 1+2=3 means
scenes for opening
and closing are sent.
i
NOTE
Scenes with IDs 12 to
15 are active only if
parameter 1 is set to
1. In this case scenes
with IDs 1 and 2 are
sent after a single click.
i