User's Manual

30
ADVANCED PARAMETERS
NOTE
Alarm state may be
cancelled earlier, as
a result of pressing
the switch or sending
the Z-Wave command
frame.
i
GROUP 40 - Dimmer 2 operation - Alarms
40. Response to General Purpose Alarm
Available settings: 0 - No reaction
1 - Turn on the load
2 - Turn o the load
3 - Load blinking
Default setting: 3 Parameter size: 1 [byte]
41. Response to Water Flooding Alarm
Available settings: 0 - No reaction
1 - Turn on the load
2 - Turn o the load
3 - Load blinking
Default setting: 2 Parameter size: 1 [byte]
42. Response to Smoke, CO or CO2 Alarm
Available settings: 0 - No reaction
1 - Turn on the load
2 - Turn o the load
3 - Load blinking
Default setting: 3 Parameter size: 1 [byte]
43. Response to Temperature Alarm
Available settings: 0 - No reaction
1 - Turn on the load
2 - Turn o the load
3 - Load blinking
Default setting: 1 Parameter size: 1 [byte]
44. Time of alarm state
Available settings: 1-32767 (1-32767 seconds)
Default setting: 600 (600s) Parameter size: 2 [bytes]
Alarm settings - reports
45. OVERLOAD alarm report (load power consumption too high)
Available settings: 0 - No reaction
1 - Send an alarm frame
Default setting: 1 Parameter size: 1 [byte]