ADVANCED PARAMETERS
35. Auto-calibration after power on
This parameter determines the trigger of auto-calibration procedure,
e.g. power on, load error, etc.
Available settings: 0 - No auto-calibration of the load after power on
1 - Auto-calibration performed after rst power
on
2 - Auto-calibration performed after each power
on
3 - Auto-calibration performed after rst power
on or after each LOAD ERROR alarm (no load,
load failure, burnt out bulb), if parameter 37 is
set to 1 also after alarms: SURGE (Dimmer 2 out-
put overvoltage) and OVERCURRENT (Dimmer
2 output overcurrent)
4 - Auto-calibration performed after each pow-
er on or after each LOAD ERROR alarm (no load,
load failure, burnt out bulb), if parameter 37 is
set to 1 also after alarms: SURGE (Dimmer 2 out-
put overvoltage) and OVERCURRENT (Dimmer
2 output overcurrent)
Default setting: 1 Parameter size: 1 [byte]
37. Behaviour of the Dimmer 2 after OVERCURRENT or SURGE
Occuring of errors related to surge or overcurrent results in turning
o the output to prevent possible malfunction. By default the device
performs three attempts to turn on the load (useful in case of mo-
mentary, short failures of the power supply).
Available settings: 0 - device permanently disabled until re-en-
abling by command or external switch
1 - three attempts to turn on the load
Default setting: 1 Parameter size: 1 [byte]
39. Power limit - OVERLOAD
Reaching the dened value will result in turning o the load. Addi-
tional apparent power limit of 350VA is active by default.
Available settings: 0 - functionality disabled
1-350 - 1-350W
Default setting: 250 Parameter size: 2 [bytes]
NOTE
Parameter 39 is rele-
vant only when pa-
rameter 58 is set to 0.