ADVANCED PARAMETERS
GROUP 30 - Dimmer 2 operation - Advanced functionality
30. Load control mode
This parameter allows to set the desired load control mode. The de-
vice automatically adjusts correct control mode, but the installer may
force its change using this parameter.
Forced auto-calibration will set this parameters value to 2.
Available settings: 0 - forced leading edge control
1 - forced trailing edge control
2 - control mode selected automatically (based
on auto-calibration)
Default setting: 2 Parameter size: 1 [byte]
31. Load control mode recognized during auto-calibration
(read only)
Available settings: 0 - leading edge
1 - trailing edge
Default setting: Parameter size: 1 [byte]
32. On/O mode
This mode is necessary while connecting non-dimmable light sourc-
es. Setting this parameter to 1 automatically ignores brightening/
dimming time settings. Forced auto-calibration will set this parame-
ters value to 2.
Available settings: 0 - on/o mode disabled (dimming is possible)
1 - on/o mode enabled (dimming is not pos-
sible)
2 - mode selected automatically
Default setting: 2 Parameter size: 1 [byte]
33. Dimmability of the load (read only)
This parameter contains an information about possibility of dimming
the load detected during calibration procedure.
Available settings: 0 - Load recognized as dimmable
1 - Load recognized as non-dimmable
Default setting: Parameter size: 1 [byte]
34. Soft-Start functionality
Time required to warm up the lament of halogen bulb.
Available settings: 0 - no soft-start
1 - short soft-start (0.1s)
2 - long soft-start (0.5s)
Default setting: 1 Parameter size: 1 [byte]
CAUTION
Modications of pa-
rameters in GROUP 30
should be performed
only by a qualied in-
staller.
!