Product Card
Alternator Physical Data
Manufactured for FG Wilson by:
Model:
No. of Bearings:
Insulation Class:
Winding Pitch Code:
Wires:
Ingress Protection Rating:
Excitation System:
AVR Model:
Overspeed:
rpm
Voltage Regulation: (Steady state)
Wave Form NEMA = TIF:
Wave Form IEC = THF:
Total Harmonic content LL/LN:
Radio Interference:
Radiant Heat:
kW (Btu/min)
- 50 Hz
- 60 Hz
Voltage Prime: Standby:
kVA kW kVA kW
Alternator
Performance Data:
Data Item
Motor Starting
Capability* kVA
Short Circuit
Capacity %
Reactances: Per Unit
Xd
X'd
X"d
Reactances shown are applicable to prime ratings.
*Based on 30% voltage dip at 0.6 power factor.
Leroy Somer
Suppression is in line with European
Standard EN61000-6
Voltage Prime: Standby:
kVA kW kVA kW
60 Hz50 Hz
Alternator Operating Data
2
0.62V04 26.024.024.0
2
0.62V03 26.024.024.0
24.0 0.620.42 26.0
2
20V
-- -
1.7811.6291.496
0.1960.1800.165
0.0980.0900.083
545759
R220
SHUNT
IP23
4
2/3 - M
H
1
LLB1514J
-
2.8 (159)
4.0%
2.0%
50
+/- 1.0%
2250
240V 230V 220V
Output Ratings Technical Data 50 Hz Output Ratings Technical Data 60 Hz