User Manual

2. Fitting
2−7
Festo P.BE−SPC200−EN en 0901d
Warning
Actuators can be activated unintentionally and the SPC200
can be damaged if modules are fitted or removed when
the power supply is switched on. Before carrying out in
stallation and/or maintenance work, switch off the follow
ing in the sequence specified:
1. the compressed air supply
2. the load voltage and operating voltage supplies of
the
SPC200.
Fitting modules Fit the modules into the rack as follows:
1. Switch off the compressed air supply and the operating
voltage supply.
2. If necessary, remove the blanking plate.
3. Hold the module by the front plate and push it into the
guide rail. Make sure that the modules are not tilted
when they are pushed in
and that the components on the
printed circuit board are not damaged.
4. Make sure that the plugs on the contact strips are cor
rectly aligned. Then gently push the module in com
pletely. The locking levers will then engage automatically
(see Fig.2/1).