User Manual
8. Diagnosis and error treatment
8−30
Festo P.BE−S PC200−EN en 0901d
Fault class 8: NC Editor, Upload/download or operation execution fault
Fault
stage
Fault
message
Operating status / fault explanation Eliminating faults
D
nnn01x08
ppp01x08
Syntax fault or non−permitted program
number entered
· Correct entry
ppp02x08 When using the control panel:
Non−permitted program number selected,
program cannot be created as it already
exists or program cannot be opened as it
does not exist.
No free memory space
When using WinPISA:
Program could not be loaded When the
fault is deleted, the memory of the SPC200
will be re−assigned.
· Correct entry
If the maximum number of NC
records is not yet reached:
· Carry out program modifica
tion with WinPISA; if necess
ary the memory will be
re−assigned.
· Load the program again
when the memory has been
re−assigned.
nnn03x08 Non−permitted record number · Correct entry
ppp04x08 No free memory space for new program · Delete unnecessary
programs and NC records
ppp05x08 Test sum fault · Servicing required
00006x08
to
0000Ax08
Fault in Upload/Download with WinPISA · Check connecting cable and
diagnostic module; if necess
ary set lower baud rate
0000Bx08 Enable signal missing · Apply a 1−signal at the
ENABLE input
0000Cx08 System has stopped, there is a 0−signal at
the STOP input
· Apply a 1−signal at the STOP
input
0000Dx08 Starting program does not exist · Correct the number of the
starting program
0000Ex08 Command not permitted in this operating
mode
· Do not use this command in
the current operating mode
or modify the operating mode
zzz = Additional information
yy = Fault number
x = Axis identifier (0 = fault is not axis−related)
ppp = Program number
nnn = NC record number of the accessing NC command