8. Diagnosis and error treatment
8−13
Festo P.BE−SPC200−EN en 0901d
8.2.2 Fault classes
Fault class 0: No fault
Fault
stage
Fault
message
Operating status / fault explanation Eliminating faults
00000000 No fault registered
Fault class 1: Initialization phase Fault in the initialization of
components and modules
Fault
stage
Fault
message
Operating status / fault explanation Eliminating faults
A
zzz01x01 Internal system fault
zzz = 001, 002: System memory fault;
perhaps the basic unit is defective
Servicing required
· If the fault occurs
more than once,
replace basic unit
zzz02x01 Faults in initializing the axis interface string
zzz = Fault location and fault type:
Fault location:
0zz: Fault on 1st. AIF string
1zz: Fault on the 2nd AIF string
Type of fault:
z00: Active fault could not be acknowledged
z01, z0B: Fault on the first measuring system
z02, z0C: Fault on
the second measuring system
z03, z09: Fault on the 1st. AIF
z04, z0A: Fault on the 2nd. AIF
z05: Fault on the 1st. CP module
z06: Fault on the 2nd. CP module
z07, z08, z0D: Bus error
· Check and if
necessary replace
modules or com
ponents on the
AIF string
· Check operating
system version in
SPC200. Is it per
missible for the
axis interfaces
used? (see also
page XVI)
zzz03x01 Defective or non−permitted component
zzz = Location number, in ascending order from
left to right (000...003 for 4, and
000...005 for 6 locations)
Replace or remove
component
zzz = Additional information
yy = Fault number
x = Axis identifier (0 = fault is not axis−related)
AIF = Axis interface