User Manual

8. Diagnosis and error treatment
8−5
Festo P.BE−SPC200−EN en 0901d
Reaction Sequence Operating status Eliminating faults
ERROR LED
ON
OFF
Switch−on phase (3...4 seconds)
or
Hardware fault, SPC200 is not
ready for communication
· None
· Servicing required
ON
OFF
No internal fault registered None
ON
OFF
Lights up briefly once when the
device is switched on
None
Flashing sequence according to the
fault class with a 1−second break
Flashes once (fault class 1)
Initialization fault
Flashes twice (fault class 2)
reserved
Flashes three times (fault class 3)
User data damaged
Flashes four times (fault class 4)
Hardware fault during running
time
Flashes five times (fault class 5)
Sequence control fault
Flashes six times (fault
class 6)
Fault in positioning task
Flashes seven times (fault 7)
Pre−parametrizing fault
Does not flash (fault class 8)
Flashes nine times (fault class 9)
Trace fault
Flashes continuously without
break Firmware deleted by user
· Install components and
modules correctly or replace
defective module
1)
2)
· (Reserved)
· Carry out Data Reset and
enter or load data again
1)
2)
· Read out fault message and
eliminate fault
1)
· Read out fault message and
eliminate fault
1)
· Read out fault message and
eliminate fault
1)
· Read out fault message and
eliminate fault
1)
· None
· Carry out Data Reset and
enter or load data again
1)
2)
· Load firmware
1)
Read out fault message and eliminate fault (see section 8.2)
2)
Or servicing required