User Manual
6. Operating the SPC200 with the control panel
6−47
Festo P.BE−SPC200−EN en 0901d
Menu SYSTEM CONTROL
SYSTEM CONTROL
RESET SYSTEM ?
Reset system
The SPC200 is reset to the status it was in when it was switched on.
A program reset and a hardware recognition are carried out here and
the axis interface string is re−initialized. This procedure can take a
certain amount of time, depending on the system configuration used.
SYSTEM CONTROL
RESET PROGRAMS ?
Reset program
Prerequisites:
there must be a 1−signal at the ENABLE input
This will have the following effects:
the NC record pointer is reset to 0
the pre−settings G90 and G02 (speed and acceleration values and
workpiece mass in initial state), as well as the positioning quality
class set in the application data become valid
the nominal value input is switched off (M12)
all settings undertaken with M10, M11, M13 or M14 are reset to the
defined standard values (parameter set for the axis, Nominal value
specification" tab)
pre−switch off values defined with G25 are reset again
direct control of the valve voltage (M39) is deactivated
all settings undertaken
with M40 and M41 are reset to the standard
values
all freely programmable outputs and the SYNC outputs are reset
the set starting programs are made available
any faults are acknowledged.
SYSTEM CONTROL
RESET ERROR ?
Reset fault
Prerequisites:
there must be a 1−signal at the ENABLE input
With this command the fault code is reset to 0.
SYSTEM CONTROL
RESET DATA ?
Reset all data to the status as at delivery
With this command all data are reset to the status as at delivery.
All user data will be lost.