Summary of Record Select mode
The Record Select operating mode supports the close
coupling of the SPC200 with a higher−order PLC/IPC.
Record Select mode
Description
Prerequisites The program must already be saved in the program memory
The system data must be entered in the configuration
The Record Select mode must be set
There must be a 1−signal at the ENABLE and STOP inputs
Operation with the control
panel
Operating functions
Stop, Reset via menu SYSTEM CONTROL on the control panel
Operation via I/O Operating functions
Select NC record via the RECBIT... inputs.
Start the selected NC record via the CLK input
Stop via the STOP input
Program reset with 0−signal at the STOP input and rising edge
at the CLK input
Fault acknowledgement with 1−signal at the STOP input and