Connection assignment of front plug X5 for the first
I/O module when operated without a field bus
module
If a field bus module is not installed, the first I/O module will
provide the following control inputs:
Inputs with control function
Pin no. Design.
1)
Address
2)
Start/Stop mode Record Select mode
1 24 V 24 V sensor supply (not with separate potential)
2 0 V 0 V (not with separate potential)
3 0 I0.0 Freely programmable RECBIT1
4 1 I0.1 RECBIT2
5 2 I0.2 RECBIT3
6 3 I0.3 RECBIT4
7 4 I0.4 RECBIT5
8 5 I0.5 SYNC_IB CLK_B
9 6 I0.6 SYNC_IA CLK_A
10 7 I0.7 STOP STOP
11 8 I0.8 START/RESET
3)
RESET
3)
12 9 I0.9 ENABLE ENABLE
1)
Designation on the module
2)
Addresses of the first installed I/O module when configured without a field bus module (I = input)
3)
RESET (Program Reset) in conjunction with 0−signal at the STOP input