Instruction Manual

1. Overview of components
1−19
Festo P.BE−CPX−SYS−EN en 0902e
Note
With a combination of connection blocks and interlinking
blocks with metal on plastic or plastic on metal, always use
the appropriate screws for the interlinking block (see
www.festo.com\catalogue):
With plastic interlinking block: thread−cutting screws
With metal interlinking blocks: screws with metric thread
1.1.3 The power supply concept of the CPX terminal
The operating and load voltages for the CPX terminal are sup
plied via the interlinking blocks (see Tab.1/5 and Tab.1/6).
These conduct the operating and load voltages to the neigh
bouring modules.
Interlinking blocks are available in various housing designs
and with alternative connections:
Type of plug con
t
Number
fi
Interlinking block in
nector of pins
plastic
version
metal
version
M18 4−pin ·
7/8" 4−pin ·
5−pin · ·
Push pull 5−pin ·
· Available
Not available
Interlinking blocks with 5−pin plug connectors enable separ
ate electrical circuits for the operating voltage for electronics/
sensors and the load voltage for outputs/valves.