Instruction Manual

B. Parameters and data of the CPX terminal
B−25
Festo P.BE−CPX−SYS−EN en 0902e
Diagnostic memory parameter: Run/stop filter 2
Function no. 3484
Description Diagnostic memory filter with which you can determine when the registering of
errors is to be started or stopped.
Bit Bit 0...2
Values
Bit 210
000
Run/stop filter 2
MN = module number, CN = channel number,
FN = error number
Description
Run/stop filter 2 inactive (presetting)
[Run/Stop 2]
[Inactive]
001 Register up to the defined FN [Rec. up to def. FN]
010 Register up to the defined FN + MN [Rec. up to def. FN + MN]
011 Register up to the defined FN + MN + CN [Rec. up to def. FN + MN + CN]
100 Register as from the defined FN [Rec. as of def. FN]
101 Register as from the defined FN + MN [Rec. as of def. FN + MN]
110 Register as from the defined FN + MN + CN [Rec. as of def. FN + MN + CN]
111 Reserved
Note The numbers are determined by means of the diagnostic memory parameters
Module, channel and error numbers" (function nos. 3485....3487).
Tab.B/26: Run/stop filter 2