Instruction Manual

B. Parameters and data of the CPX terminal
B−13
Festo P.BE−CPX−SYS−EN en 0902e
System parameter: System start
1)
Function no. 4402
Description With this parameter you can determine the start−up reaction of the CPX terminal
and save all current parameter settings and the current CPX equipment status.
Bit Bit 6
Values
Bit 6
System start *)
Description
[System start]
0 System start with default parametrising (factory set
ting) and current CPX equipment status; external para
metrising is possible (presetting)
[Default parameters]
1 System start with saved parametrising and saved CPX
equipment status; parameters and CPX equipment
status are saved remanently; external parametrising is
blocked; the M−LED on the CPX bus node lights up.
[Saved parameters]
Note If bit 6 is set to 1, the current parameter settings will be frozen" (write−protec
ted) and the current CPX equipment status will be saved, except for bit 6 itself
and the module parameter Force channel X."
Recommendation: Select System start with default parametrising and current
CPX equipment status." The desired parametrising can
then be created in the
start−up phase or after fieldbus interruptions e.g. by the plug−in module or the
scanner/bus master (depending on the fieldbus used). If System start with
default parametrising and current CPX equipment status" is active, the factory
settings for all module and system parameters will become valid after Power
On.
1)
This parameter does not exist with the CPX−FEC in the operating modes Stand Alone and Remote
Controller (control function active).
Tab.B/8: System start