Instruction Manual

B. Parameters and data of the CPX terminal
B−9
Festo P.BE−CPX−SYS−EN en 0902e
System parameter: Monitoring
Function no. 4401
Description The monitoring of short circuit/overload and undervoltage for the complete CPX
terminal can be activated or deactivated (suppressed). Active monitoring causes
the following. An error registered by the module will be:
Sent to the higher−order fieldbus master
Entered, if applicable, in the diagnostic memory (depending on filter settings)
Entered in the module diagnostic
data and, if applicable, in the status bits
Displayed by the module common error LED
Displayed by the red SF−LED on the CFX bus node
Bit
0
Monitoring
Description
Short circuit/overload in sensor supply (SCS)
[Monitor]
[Monitor SCS]
1 Short circuit/overload at the outputs (SCO) [Monitor SCO]
2 Undervoltage at outputs (V
OUT
) [Monitor Vout]
3 Undervoltage of valves (V
VAL
) [Monitor Vval]
4 Short circuit at valves (SCV) [Monitor SCV]
5...7 Reserved
Values 1 = active (presetting)
0 = inactive
[Active]
[Inactive]
Note Monitoring can also be set separately for each module (see module parameter
monitoring CPX module).
The method of operation of the channel fault LED remains unaltered.
Tab.B/4: Monitoring short circuit/overload/undervoltage