Instruction Manual
A. Technical appendix
A−4
Festo P.BE−CPX−SYS−EN en 0902e
Severity
level
Vibration Shock Continuous shock
1 0.15 mm path at 10 ... 58 Hz;
2 g acceleration at
58 ... 150 Hz
±15 g at 11 ms dura
tion; 5 shocks per
direction
±15 g at 6 ms duration;
1000 shocks per direction
2 0.35 mm path at 10 ... 60 Hz;
5 g acceleration at
60 ... 150 Hz
±30 g at 11 ms dura
tion; 5 shocks per
direction
−
Operating voltage for fieldbus interface
Nominal value
Tolerance
See manual for the specific CPX bus node
Caution
Short circuits can cause damage.
Provide external fuse protection for the system supply and
additional supplies. The permissible current per pin at the
supply is:
7/8" plug, 4−pin: max. 10A
1)
2)
7/8" plug, 5−pin: max. 8A
1)
M18 plug (4−pin): max. 16A
2)
Push−pull plug (5−pin): max. 16A
1)
Limited by the specification of the connected plug con
nector. Values apply for plug connectors from Festo Acces
sories. If using third−par ty products, comply with the appli
cable specifications.
2)
Please note that with a 4−pin system supply via pin
0V", the sum of both currents of the operating and load
voltages flows.