Instruction Manual
A. Technical appendix
A−3
Festo P.BE−CPX−SYS−EN en 0902e
A.1 Technical data
General
Temperature range:
Operation
Storage/transport
−5 °C ... + 50 °C
−20 °C ... + 70 °C
Relative air humidity 95 %, non−condensing
Protection against electric shock
(protection against direct and indirect con
tact as per EN 60204−1/IEC 204)
By means of PELV power supply unit
(Protected Extra Low Voltage)
Protection class as per EN 60 529 (plug con
nector inserted or provided with protective
cap)
Depending on the connections and configuration
used. The lowest protection class of the weakest
components used is always valid for the complete
device (see manual for the relevant module)
e.g. terminal connections: IP 20
e.g. M8 and M12 connections: IP 65 and IP67
Electromagnetic compatibility
Interference emission
Interference immunity
See declaration of conformity (www.festo.com)
See declaration of conformity (www.festo.com)
Vibration and shock
2)
Vibration
Shock
Continuous shock resistance
Tested according to DIN/IEC 68/EN 60068
part 2−6;
When mounted on an H−rail
3)
: Severity level 1
When fitted on a wall
3)
: Severity level 2
Tested according to DIN/IEC 68/EN 60068
part 2−27;
When mounted on an H−rail
3)
: Severity level 1
When mounted on a wall
3)
: Severity level 2
Tested according to DIN/IEC 68/EN 60068
part 2−29;
With H−rail and wall mountings:
Severity level 1
1)
The component is intended for use in industrial environments.
2) See following table for explanations of the severity levels.
3) For MPA valve terminals, the vibration and shock resistance depends on the number of installed
sub−bases (see pneumatic description).