5.1.2 CPX−specific LEDs
PS (power system) power sensor/logic supply
LED (green) Sequence Status Meaning / error handling
LED lights up
ON
OFF
No error. Operating vol
tage/sensor supply applied
LED f
las
h
es
ON
OFF
Operating voltage/sensor
supply outside the tole
rance range
Eliminate undervoltage
LED
flashes
ON
OFF
Internal fuse for the opera
ting voltage/sensor supply
has responded.
1. Eliminate short circuit/overload on
module side.
2. Depends on the parametrisation of
the module (module parameter):
· The sensor supply voltage will be
switched on again automatically
after the short circuit has been
eliminated (default)
· Power Off/On is necessary
LED is off
ON
OFF
The operating voltage/sen
sor supply is not applied
Check the operating voltage connec
tion of the electronics
PL (Power Load) power load supply (outputs/valves)
LED (green) Sequence Status Meaning / error handling
LED lights up
ON
OFF
No error. Load voltage ap
plied
No
LED flashes
ON
OFF
Load voltage at the system
supply or additional supply
outside the tolerance
range
Eliminate undervoltage