A. Notes on commissioning and service
A−5
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Data reset
An axis data reset (see section A.3.4) resets the axis data of
the CMAX to the delivery status. In this status the CMAX con
tains no setpoint configuration. Parametrisation is required to
activate the controller.
The CMAX can be configured with or without connected com
ponents (in the office"). If the valve and
the sensor interface
have been connected, the CMAX will perform automatic hard
ware recognition after switching it on. The data found in the
course of this are adopted by the FCT.
If commissioning is performed without components, all the
data needs to be entered.
In order to indicate the status of parametrisation, the display
reads status C00 ... C03 (can also be queried by reading
PNU 1102:02) These statuses mark the respective action re
quired next.