5. Parameter
5−37
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Current warning to be displayed in FCT
PNU PNU: 226 Index: 1 Max index: 1 Class: Var Data type: int32
Values Without unit
Default: 0 Minimum: Maximum:
The PNU 226 contains the warning number the FCT is supposed to display. Warnings are not dis
played on the CMAX display.
ý The parameter value cannot be changed.
o Writing permissible only in commissioning/parametrising mode with disabled controller.
o This parameter can be written by FCT without higher−order controller.
o After writing, controller recalculation is carried out.
Fault status for FCT
PNU PNU: 227 Index: 1 ... 89
Max index: 89 Class: Array Data type: bitarray
Values Default: 0000 0000 0000 0000 0000 0000 0000 0000
Write:
The bit−encoded error status allows to indicate the exact status of a fault message. The coding
is identical to the coding of the additional information in PNU 203. For the description, see
section 4.3.3.
ý The parameter value cannot be changed.
o Writing permissible only in commissioning/parametrising mode with disabled controller.
o This parameter can be written by FCT without higher−order controller.
o After writing, controller recalculation is carried out.
Filter diagnostic events
PNU PNU: 228 Index: 1
Max index: 3 Class: Struct Data type: bitarray
Values Default: 0000 0000 0000 0000 0000 0000 0000 0000
Write: 0000 0000 0000 0000 0000 0000 0000 xxxx
This setting can be used to define the scope of the records. By default the CMAX records very large
quantities of information. Not all are equally important. Certain information can selectively be ex
cluded from the records, see section 4.4. In this way only the most important events are included in
the diagnostic memory. For allocation, see 4.4.
o The parameter value cannot be changed.
o Writing permissible only in commissioning/parametrising mode with disabled controller.
o This parameter can be written by FCT without higher−order controller.
o After writing, controller recalculation is carried out.