User guide
4. Faults and diagnostics
4−25
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Fault group 5 system error B
CPX error group 105 (CPX−MMI: [System error B] ) continued
No. Message Cause/description Error handling Type
3)
54 Operating voltage over
load on the controller
Short circuit in the
cables of the axis string
(between controller and
valve or valve and sen
sor interface).
· Check the cables and
modules in the axis
string (e.g. for a cable
break age), replace if
necessary.
Level: F2
Reset: F
Info: x
Defect in the CMAX con
troller
· Check CMAX, ex
chan g e if necessary.
Defect in the valve · Check the cables and
valves step by step
and exchange, if
necessary.
Defect in the sensor
(measuring system) or
sensor interface
· Check the cables and
sensor or sensor inter
face step by step and
exchange, if necessary.
55 Load voltage drop: The
power pack rating is not
sufficient
The load voltage
dropped several times
when sequencing to the
valve.
The power pack rating is
probably not sufficient
· Check total load of the
power pack and use a
more powerful power
pack. Also take into
accou n t the loads at
the valve output
(clam p i n g unit etc.).
Level: F2
Reset: F
Info: x
56 Supply pressure is in
sufficient to safely move
or hold the load
Insufficient supply pres
sure was detected dur
ing homing.
· Check supply pressure
and increas e if
necessary.
· Check parametrisation
of the supply pressure.
Level: F1
Reset: R
Info: x
57 Timeout diagnostic in
terface: FCT device con
trol was deactivated
Connection between PC
and CPX node inter
rupted.
· Check the cables.
Level: W
Reset: R
Info: x
Communication break
down due to FCT.
· Restore connection.
1)
Level: fault level, see section 4.2.3; (can alternatively be parametrised as a warning or error)
Reset: behaviour upon reset, see section 4.2.4
Info: = no info; x = additional info, see FCT or section 4.3.3