4. Faults and diagnostics
4−10
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Fault group 0 configuration error
CPX error group 100 (CPX−MMI: [Configuration error]) continued
No. Message Cause/description Error handling Type
1)
05 Project not loaded com
pletely or block down
load active
The controller cannot be
enabled because the
nominal configuration is
not yet complete.
(Configuration status
C00, C01 or C02).
· Complete the nominal
configuration, e.g.
project download.
Level: F2
Reset: R
Info:
The controller cannot be
enabled because block
download is still active.
· Terminate block down
load. Check PLC pro
gram (parametrisa
tion) and correct if
necessary.
08 Cylinder, valve or
sensor interface was
exchanged
2)
The serial number of a
component on the axis
string has changed:
Drive (measuring
system).
Valve.
1. Adopt serial number of
the component.
2. Run movement test
(recommendation).
3. Carry out identification
(recommendation).
Level: W
Reset: F
Info: x
09 Faulty parameter in the
project
Software end positions
inconsistent, see section
B.2.4.
· Read diagnostics mem
ory, determine para
meter via additional in
formation.
· Check and correct soft
ware end positions.
Level: F2
Reset: N
Info: x
Invalid values concerning
axis parameters or hard
ware configuration.
· Check parameters and
correct.
1)
Level: fault level, see section 4.2.3
Reset: behaviour upon reset, see section 4.2.4
Info: = no info; x = additional info, see FCT or section 4.3.3
2)
The movement test is reset to avoid tubing errors. The CMAX has C03 status. The movement test
should then be run once more.