Owner's manual
5. Diagnostics and error handling
5−9
Festo P.BE−CPX−CMAX−SYS−EN en 0908NH
Malfunction group 0 Configuration error
CPX error group 100 (CPX−MMI: [Configuration error]) Continued
No. Message Cause/description Error handling Type
1)
05 Project is not completely
loaded or block down
load is still active
The controller cannot be
enabled because the
target configuration is not
yet complete. (Configur
ation status C00, C01 or
C02).
· Complete the target
configuration, e.g.
project download.
Error
level: F2
Reset: R
The controller cannot be
enabled because the
block download is still ac
tive.
· End the block down
load. If necessary,
check the PLC program
(parameterisation)
and correct.
08 Cylinder, valve or sensor
interface was replaced
2)
The serial number of a
component on the axis
string has changed:
Drive (displacement
encoder)
Valve
1. Accept the serial
number of the
component.
2. Carry out a movement
test (recommenda
tion):
3. Carry out identification
(recommendation):
Error
level: W
Reset: F
09 Project contains incorrect
parameters
Software end positions
inconsistent.
· Read out diagnostic
memory, determine
parameters via addi
Error
level: F2
Reset: N
Invalid values for axis
parameters or hardware
configuration.
parameters v
i
a a
ddi
tional information.
· Check the parameters
and correct.
R
eset:
N
1)
For the error level and reset type, see section 5.2.3.
2)
To avoid tubing errors, the movement test is reset. CMAX has the status C03. The movement test
should be executed again afterwards.