Submittal Sheet

2
THERMOSWITCH
®
CONTROLLERS -100 TO 600
º
F/-73 TO 316
º
C
Thermoswitch Unit Type
and
Dimensions
(Inches/mm)
Description
Catalog
Number
Temperature
Range
Contact
Operation
on Temp
Rise
Shell and
Head
Material
Approximate
Degrees
changes per
full turn of
adjusting
sleeve
Extreme
Temperature
Exposure
Current
Rating
Factory Temp
Setting
Tolerance (MOD. #3)
Applicable
Modifications
Applicable
Special Features
See Modifications and Special
Features Section
The basic element of all
THERMOSWITCH
®
controllers. Has all the
desirable features of the ideal thermostat -
high sensitivity, wide adjustment range,
small size, rugged construction, vibration
resistance, and low cost. The unit can be
inserted into a .625 in. (15.88 mm) reamed
hole. Approximate weight is 2.5 ounces (70
grams).
01-017000-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
90ºF/50ºC
Unless otherwise specified, all ratings apply to non-inductive
loads such as heaters or resistors. Tungsten filament lamps
have an in rush 10 to 15 times the steady state current. Do
not exceed ratings.
1
2
3
4
14
31
34
35
01-017021-000 Closes 80ºF/45ºC
01-017002-000
-100 to +600ºF
-73 to +316ºC
Opens
300 Series
S.S. Shell
110ºF/60ºC
01-017023-000 Closes 100ºF/55ºC
Has all the features of the Cartridge Type
plus the addition of a pipe thread for
mounting. Approximate weight is 5 ounces
(140 grams).
01-017100-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
80ºF/45ºC UNITS THAT
OPEN
ON
TEMPERA-
TURE RISE:
100ºF/73ºC
indefinitely and
100ºF/55ºC
above set point
for one hour
maximum
UNITS THAT
CLOSE
ON
TEMPERA-
TURE RISE:
-100º to
+400ºF/
-73º to 204ºC
-100ºF/-73ºC
indefinitely and
500ºF/260ºC
for one hour
maximum
-100º to
+600ºF/
-73º to +316ºC
-100ºF/-73ºC
indefinitely
and
700ºF/370ºC
for one hour
maximum
*
AC
10 amps
120 volts
5 amps
240 volts
(non-
inductive)
DC ratings
consult
Fenwal
UNITS THAT OPEN
ON
TEMPERATURE RISE
±5ºF from +32 to +100ºF
±3ºF or ±2% of Setting
Value (whichever is
greater)
From 100 to 600ºF
UNITS THAT CLOSE
ON
TEMPERATURE RISE
±5ºF or 3%
of Setting Value
(whichever is greater)
1 thru 14
31
34
35
01-017121-000 Closes 75ºF/40ºC
01-017102-000
-100 to +600ºF
-73 to +316ºC
Opens 300 Series
S.S. Shell
Brass
Head
100ºF/55ºC
01-017123-000 Closes 90ºF/50ºC
This unit has the same mounting as the
Cartridge Type but is designed so
modifications may be included. It also can
be inserted into a .625 in. (15.88 mm)
reamed hole. Approximate weight is 3
ounces (84 grams).
01-017200-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
80ºF/45ºC
1 thru 14
31
34
01-017221-000 Closes 75ºF/40ºC
01-017202-000
-100 to +600ºF
-73 to +316ºC
Opens 300 Series
S.S. Shell
Brass
Head
100ºF/55ºC
01-017223-000 Closes 90ºF/50ºC
Has all the features of the Block Head Type
except a mounting flange has been
provided. Approximate weight is 4 ounces
(112 grams).
01-017300-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
80ºF/45ºC
1 thru 14
31
34
01-017321-000 Closes 70ºF/40ºC
01-017302-000
-100 to +600ºF
-73 to +316ºC
Opens
300 Series
S.S. Shell
100ºF/55ºC
01-017323-000 Closes 90ºF/50ºC
Has electric conduit junction box
containing terminal block and temperature
adjusting dial and knob. Extended
hexagonal section with pipe thread permits
easy mounting into tapped hole of boss,
immersing shell into fluid medium to be
controlled.
01-017800-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
125ºF/70ºC
1
3
31
34
01-017821-000 Closes 75ºF/40ºC
01-017802-000 -100 to +600ºF Opens 300 Series
S.S. Shell
Brass
Head
160ºF/90ºC
01-017823-000 -73 to +316ºC Closes 90ºF/50ºC
The Coupling Head Type has a hexagonal
mounting section with pipe threads at each
end. This unit may be directly attached to
electrical conduit. Approximate weight is 5
ounces (140 grams).
01-018000-000 -100 to +400ºF
-73 to +204ºC
Opens
Brass
80ºF/45ºC
1
2
3
4
14
31
34
35
01-018021-000 Closes 75ºF/40ºC
01-018002-000
-100 to 600ºF
-73 to +316ºC
Opens 300 Series
S.S. Shell
Brass
Head
100ºF/55ºC
01-018023-000 Closes 90ºF/50ºC
Recognized under the Components Program of Underwriters Laboratories, Inc. (XAPX2)
Underwriters Laboratories Listed (XAPX)
Certified by Canadian Standards Association (Class 481302) CSA File No. LR7378
* UL and CSA units rated for AC operation only.
TEMPERATURE OFFSET VALUES
DUE TO PRESSURE (APPROX. ONLY)
Pressure PSI
Set Point Offset
100
+3°F/2 C°
200
+6 F/3 C°°
300
+9 F/5 C°°
400
+12 F/7 C°°
500
+15 F/8 C°°
Collapsing pressure (brass shell) 1400 psi at room temperature
Collapsing pressure (S.S. shell) 3,500 psi at room temperature