Installation
ID ISC.LRU1002
FEIG ELECTRONIC GmbH
Page 20 of 31
M61110-5e-ID-B.docx
4.4.4.
Relay output on connector X4
There are 2 relay outputs (normally open) available on connector X4.
Figure 16: Relay outputs REL1 / REL2
Table 12: Pin Assignment Relay Outputs REL1 / REL2
CAUTION:
The relay outputs are configured for max. 24 V DC / 2 A constant load.
The switching current must not exceed 1A.
The relay outputs are intended for switching resistive loads only. If an inductive load is con-
nected, the relay contacts must be protected by means of an external protection circuit.
Figure 17: External wiring of the relay outputs
Pin Number
at Connector X4
Pin Assignment
5
REL1-NO
6
REL1-COM
15
REL2-NO
16
REL2-COM