User's Manual

running protection time compressor will not runnig it need pass three miniute
then can start at any mode.
Compressor need three minutes to stop running before last running.Its
function is prevent compressor overload.
Defrost:
Defrost condition: when evaporator temperature lower or equal -1.5C
continue over 20minutes it will start deforest action. But when evaporator
temperature over 0C, system will stop counting time.
Defrost action: turn off the compressor, turn on the fan, keep last mode and
correspondent led will on, keyboard also validate.
Defrost finish condition:
1.
2.
3.
Evaporator temperature over 0
C.
Compressor off, fan on, for 6 min
press MODE/POWER to turn off
Defrost closing action: when closing defrost, system enter last mode and start
running.
When Evaporator temperature over 0
C and then fan on for 6 minutes then
finish deforest. Or you can press MODE/POWER to turn off dierectly.
HUMIDITY DISPLAY
Display humidity rang is 20%~98%, when the humidity lower 20%, humidity
displays 20% when humidity over 98%, humidity display 98%.
TESTING MODE
Pressing POWER/MODE key before power plug and then plug in system will
enter entering on-line testing mode, light and display all bright, and then you
can release POWER/MODE key .
Pressing POWER/MODE key again, turn on the fan, bring out the room
humidity, Continuous led bright, other led off.
Pressing POWER/MODE key again, the compressor on, fan is running at the
same time, bring out the room humidity, 45%-55% led on, other led off.